Air Quality Signal (MF420-IR Mobile)
The Air Quality Signal has been designed especially to monitor the ambient air quality in interiors. It determines, by using a specific two-beam infrared photometer (NDIR) , developed and produced our company, the absolute CO2 concentration in the ambient air (atmospheric partial pressure). The device is constantly self-monitoring. The system reports malfunctions of hardware and software and is low-maintenance under normal applications thanks to the NDIR technology - we recommend at least an annual inspection.
The air quality signal can be mounted on the wall or simply placed on a shelf and is equipped with an AC adapter for power supply. An installation by a specialist is not required. A traffic-light function, via three LEDs indicates the carbon dioxide concentration in the air and thus the air quality.
The Air Quality Signal measures the CO2 concentration between 0-3000 ppm. The standard threshold values are configured in accordance with the recommendation of the German Federal Environmental Agency. The threshold values can be factory customized individually, within their measuring range, according to customer requirements. Optionally the air quality signal can be ordered with an integrated data logger for recording of the measurements. At the product MF420-IR mobile with data logger, readings for later analysis on a PC can be stored. Measurement values can be stored up to one week in a 60-second clock pulse. The accompanying analysis software provides the ability to display the data graphically or to export for post-processing into a spreadsheet program. The device complies with the generic standards EN 61000-6-2 and EN 61000-6-4 and thus the EMC Directive 2004/108/EC. The device thanks to its NDIR-Technology is low-maintenance - we recommend at least an annual inspection. For more details, please refer to the technical data or ask our contact person.
Measuring ranges and threshold values
< 1500 ppm
LED green
1500 ppm to < 2500 ppm
LED yellow
2500 ppm to < 3000 ppm
LED red
> 3000 ppm
LED red flashing
When exceeding the first threshold value (1500 ppm) a short audible signal will sound and the LED light turns from green to yellow. If the second threshold value (2500 ppm) is exceeded, the LED light turns from yellow to red and the device again triggers an audible alarm. If the third threshold value (3000 ppm) is exceeded, the red LED flashes continuously. If the CO2 concentration falls below the first threshold, the device goes back to the ground state and the green LED lights up again.Data Logger
Certifications
Maintenance and service
Product Name Product Features Product Code
MF420-IR Mobile
without data logger
measuring range 0 - 3000 ppmG4G0-I09NP-0000
MF420-IR Mobile with Data Logger
with data logger
measuring range 0 - 3000 ppmG4G0-I09NP-C100
Principle of Measurement
NDIR (two-beam infrared photometer)
Power Supply
Power Adapter
230 V AC
Current
approx. 350 mA
Ambient Temperature
-10°C to +50°C
Air Pressure
900 hPa to 1100 hPa
Permissible Humidity
15 to 95% relative humidity
non condensing
Optical Display
green LED
[CO2] < 1,500 ppm
yellow LED
1,500 ppm < [CO2] < 2,500 ppm
red LED
[CO2] > 2,500 ppm
red LED flashing
[CO2] > 3,000 ppm
Housing
Plastic white
Protection class
IP 30
Weight
approx. 150 g
Dimensions (L x W x H)
78 x 78 x 35 mm
Product Name Product Features Product Code
Configuration set
Set consists of:
- CD with configuration software for data logger
- Connection cableZ0A0-D0002
Plug power Supply
230V AC Plug power Supply
Z4A0-C0004
Concealed Power Supply
230V AC power supply for mounting in a flush mounted box
Z2A0-C0003
Acrylic Display
Display for mounting an air quality signal for presentation purposes
Z0A0-B0001